Ventilation from heat load and temperature rise calculator

Engineering calculators (Beta)

Use a sensible-heat balance to compare required ventilation with actual airflow.

Inputs

Choose units and enter numbers. Full-width digits and fractions such as 1/8 or 1 3/8 are accepted. Changing a unit converts the entered value.

Results

Reference calculation only. Results do not certify suitability for an actual design or its safety.

Diagram

Inputs: select a blue symbol to edit Results: red-orange values and lines

Formula and applicability

Qreq=P/(ρcpΔTlim); ΔT=P/(ρcpQ); Premovable=ρcpQΔTlim.

Displayed values are rounded. Diagrams illustrate the calculation conditions. Initial material and fluid properties are examples; replace them with values for the actual material, temperature and conditions.

Reference
Using this information as a reference

Equations assume particular loads, supports and deformation ranges. Check inputs, units and the applicability of each equation. Diagrams explain conditions; they are not manufacturing drawings or proof of safety.

Material values are typical values or reference ranges, not certified product properties or ready-to-use design allowables. They vary with standards, product form, dimensions, temper and temperature. Check the specifications and inspection certificates for the actual product.

Displayed safety factors and checks apply only to the supplied inputs and calculation model. They do not automatically establish the safety of a complete design, including code compliance, service life, fatigue or joints. For actual design, manufacture and use, separately verify applicable regulations and standards, product specifications, and the necessary tests and engineering review.

この計算で求められること

制御盤などの顕熱収支から必要換気量を求め、実風量と比較します。

入力・結果・適用条件を確認する

選択した形状・計算方法により、使う項目は変わります。実際の計算は上の図と入力欄で行えます。

主な入力

  • 空気が持ち去る必要のある発熱 P (W / kW / mW)
  • 許容する吸気からの温度上昇 ΔTlim (K / °C difference / °F difference)
  • 吸気の空気密度 ρ(入力例) (kg/m³ / g/cm³ / g/L)
  • 空気の比熱 cp(入力例) (J/(kg·K) / kJ/(kg·K) / J/(g·℃))
  • 圧損を考慮した実風量 Q (m³/h / m³/min / L/min)

得られる結果

  • 必要な換気量 Qreq (m³/h)
  • 実風量での理論温度上昇 ΔT (K)
  • 許容温度上昇で運べる熱量 (W)
  • 必要風量/実風量 (%)

計算式の概要

Qreq=P/(ρcpΔTlim); ΔT=P/(ρcpQ); Premovable=ρcpQΔTlim.

十分に混合された空気の定常顕熱収支です。Pは換気で除去すべき正味の熱量。壁からの伝熱を差し引くなら別途評価してください。ファンの自由吹出風量ではなく、フィルター・流路の圧損時の実風量を入力します。短絡流、局部高温、湿度・潜熱、外気温の変動、ファン故障・騒音は判定しません。

現在選択中の方法には、操作欄の「計算式・適用条件」を使ってください。参考計算であり、設計全体の安全性を保証するものではありません。

関連する計算

What this calculator does

Use a sensible-heat balance to compare required ventilation with actual airflow.

Inputs, outputs and applicability

The selected model determines which of these inputs and outputs apply. Use the working diagram and input panel above to calculate.

Inputs

  • Heat P to be removed by ventilation (W / kW / mW)
  • Allowed temperature rise above intake ΔTlim (K / °C difference / °F difference)
  • Intake air density ρ (example) (kg/m³ / g/cm³ / g/L)
  • Air specific heat cp (example) (J/(kg·K) / kJ/(kg·K) / J/(g·℃))
  • Actual airflow Q at system pressure loss (m³/h / m³/min / L/min)

Calculated results

  • Required ventilation Qreq (m³/h)
  • Ideal temperature rise ΔT at actual airflow (K)
  • Heat removable at allowed rise (W)
  • Required / actual airflow (%)

Formula overview

Qreq=P/(ρcpΔTlim); ΔT=P/(ρcpQ); Premovable=ρcpQΔTlim.

Steady sensible-heat balance for well mixed air. P is net heat assigned to ventilation; wall heat transfer must be assessed separately if deducted. Enter actual airflow at filter/duct pressure loss, not free-air fan rating. Short-circuit airflow, hotspots, humidity/latent heat, changing ambient temperature, fan failure and noise are excluded.

The displayed formula and conditions in the working panel apply to the currently selected model. Reference calculation only; it does not certify a complete design.

Related tools